Benefits of Fire Door Commissioning

This guest post is provided by our #FireDoorSafetyWeek partner, Aegis Fire Barrier Consultants, and is written by, Justin B. Biller, P.E., CHFM, CLSS-HC, CFPS | AEGIS Technical Director.



Doors are a major concern for building owners and facility managers. Ongoing maintenance of doors and architectural hardware represents a significant cost margin to building owners. Nowhere, is this more true than for healthcare facility and engineering managers where building footprints are vast - often in excess of 1 million square feet or more. Maintaining all doors in large facilities is always a challenge, but of even higher concern for healthcare engineers is fire and smoke barrier management, wherein door maintenance is a critical component. This point is not lost on a highly accomplished architect, Amanda Adams AIA, who has spent much of her career in significant restoration projects – she has noted first- hand how important fire and smoke door assemblies become in sustaining code compliance, providing a safe and healthy environment for building occupants, and in achieving her overall architectural vision for a space. Ms. Adams highlighted this point to us at AEGIS, wherein she states,


“the foremost requirement of architecture is shelter. This ranks above aesthetics and creative efforts. All building occupants - users, visitors, tenants, residents - expect a building to provide shelter from the elements. At times, emergency situations arise that cause a building to offer shelter or protection from internal threats (often this is a fire threat)....whether that be protect in place or provide a safe exiting scenario. Passive life safety systems hold top priority in life safety; active systems increase safety and provide additional time. Properly functioning fire doors are a critical basic component to the passive system. A door must fit properly in its frame. Closing hardware must work properly. Positive latching hardware completes the barrier.”

The added strain on fiscal responsibilities for healthcare facilities to “do more with less” heightens the need to challenge installers to do the work right the first time – it is often noted on annual inspections of fire and smoke door assemblies that the ongoing challenges to maintenance stem from improper installation (i.e., improperly plumbed door frame and jamb, incorrect or insufficient hardware, incorrect door or glazing type, etc.).
According to the Door Security and Safety Foundation, although doors only represent 2% of a typical construction budget, on average more than 30% of punch-list items are door-related. It is, therefore, the opinion of many within the industry that it is in the best interest of building owners to verify fire and smoke doors are installed properly from the outset – a determination that committee members of NFPA 80, Standard for Fire Doors and Other Opening Protectives also found imperative. In its most current published editions (2016 and 2019), NFPA 80 prescribes in section 5.2.1 that “upon completion of the installation” these assemblies are to be inspected and tested.
Here at AEGIS we believe as well that a comprehensive survey of door installation during construction benefits the building designer and can dramatically decrease ongoing maintenance costs associated with fire and smoke door assemblies. We are here to help you implement this on your next project and can work with your design team through specification and installation through final punch-out.
What is Fire System Commissioning (FCx)
NFPA 3, Recommended Practice for Commissioning of Fire Protection and Life Safety Systems delineates that the commissioning and integrated testing process would include both, active and passive components of fire protection systems. Commissioning is a procedure of verifying a quality process from design inception through development and construction and extends through the life of the building by ongoing maintenance and operations. Passive fire protection systems, including fire and smoke rated door assemblies, serve as a primary component for most building life safety systems with varying degrees of complexity (based on factors such as occupancy and building geometry). Fire and smoke rated doors are often integrated with fire and life safety systems such as fire alarm, sprinkler, smoke control, and emergency electrical systems, thus it becomes imperative for the fire commissioning team (FCxT) to include qualified fire door commissioning agents (Cx) to be employed. Along with NFPA 3, NFPA also developed NFPA 4, Standard for the Integrated Fire Protection and Life Safety System Testing to work in concert with the recommended practices of commissioning, outlined in NFPA 3, to accomplish this task.
AEGIS with its partnerships with engineers and architects, has the practical experience and expertise to support your commissioning team with passive fire protection system components.



Smoke Gasketing and Edge Sealing in Healthcare Occupancies


This guest post is provided by our #FireDoorSafetyWeek partner, Aegis Fire Barrier Consultants, and is written by, Justin B. Biller, P.E., CHFM, CLSS-HC, CFPS | AEGIS Technical Director.



Do corridor doors require smoke gasketing in healthcare occupancies (which are classified as Group I-2 under the International Building Code® (IBC)?


There is often confusion encircling this question with facility managers, designers, and even fire door inspectors. Gasketing is often perceived as an ambiguity in the codes. This fire door component is routinely missed during design and construction, and often leads to further confusion during the life cycle of the building. The question is multi-faceted as there is various criterion to consider.

This is the final installment of a three part series that addresses the more common questions that we have noted in our work with fire and smoke door code compliance. Parts 1 and 2 of the series can be accessed from the Aegis Fire Barrier blog page.

Part 1. When is edge sealing specifically required for fire protection rated doors?
Part 2. Do fire and smoke rated doors require smoke gasketing in healthcare occupancies which are classified as Group I-2 under the International Building Code® (IBC)?
Part 3. Do corridor doors require smoke gasketing in healthcare occupancies (which are classified as Group I-2 under the International Building Code® (IBC)?

For a general listing classification of protection methods, reference to UL is helpful in understanding the parameters of installation regarding Gasketing and Edge-sealing Materials for Fire Doors, Positive-pressure Tested, GVYI.

To address the question – do corridor doors require smoke gasketing in healthcare occupancies (which are classified as Group I-2 under the International Building Code® (IBC), in general the following code excerpts from the model codes are included below.

Corridor Doors - NFPA 101, Life Safety Code, 2012
“18.3.6.2* Construction of Corridor Walls. 18.3.6.2.1 Corridor walls shall be permitted to terminate at the ceiling where the ceiling is constructed to limit the transfer of smoke. 18.3.6.2.2 No fire resistance rating shall be required for corridor walls. 18.3.6.2.3* Corridor walls shall form a barrier to limit the transfer of smoke.”

“18.3.6.3* Corridor Doors. 18.3.6.3.1* Doors protecting corridor openings shall be constructed to resist the passage of smoke, and the following also shall apply: (1) Compliance with NFPA 80, Standard for Fire Doors and Other Opening Protectives, shall not be required. (2) A clearance between the bottom of the door and the floor covering not exceeding 1 in. (25 mm) shall be permitted for corridor doors. (3) Doors to toilet rooms, bathrooms, shower rooms, sink closets, and similar auxiliary spaces that do not contain flammable or combustible material shall not be required to be constructed to resist the passage of smoke.”

As regards the application of NFPA 101 requirements for corridor walls and doors, it is important to recognize the distinction that this code makes from IBC, wherein it does not require corridor walls to be smoke partitions – note the explanatory annex language below specific to this issue:

“A.18.3.6.2.3 While a corridor wall is required to form a barrier to limit the transfer of smoke, such a barrier is not required to be either a smoke barrier or a smoke partition — two terms for which specific Code definitions and requirements apply.”

It is also important to note specifically, that NFPA 101 indicates that gasketing is NOT REQUIRED for corridor doors – note this explanatory language below:
“A.18.3.6.3.1 Gasketing of doors should not be necessary to achieve resistance to the passage of smoke if the door is relatively tight-fitting.”

Corridor Doors – International Building Code, 2012
“407.3 Corridor wall construction. Corridor walls shall be constructed as smoke partitions in accordance with Section 710. 407.3.1 Corridor doors. Corridor doors, other than those in a wall required to be rated by Section 509.4 or for the enclosure of a vertical opening or an exit, shall not have a required fire protection rating and shall not be required to be equipped with self-closing or automatic-closing devices, but shall provide an effective barrier to limit the transfer of smoke and shall be equipped with positive latching. Roller latches are not permitted. Other doors shall conform to Section 716.5.”

“710.5.2.2 Smoke and draft control doors. Where required elsewhere in the code, doors in smoke partitions shall meet the requirements for a smoke and draft control door assembly tested in accordance with UL 1784. The air leakage rate of the door assembly shall not exceed 3.0 cubic feet per minute per square foot (0.015424 m3/(s • m2)) of door opening at 0.10 inch (24.9 Pa) of water for both the ambient temperature test and the elevated temperature exposure test. Installation of smoke doors shall be in accordance with NFPA 105.”

Conclusion
The IBC again is more stringent in its application than NFPA 101 is for this requirement – note the ICC commentary for this section which clearly identifies corridor doors are to meet UL 1784:
“Only doors in smoke partitions that are required elsewhere in the code to be smoke and draft control doors must comply with section. Section 407.3.1 requires corridor doors in Group I-2 to ‘limit the transfer of smoke’; therefore, those doors must meet this section.”
As such, IBC does require corridor doors in I-2 occupancies to meet UL 1784. This results in the effect that life safety surveys involving the use of NFPA 101, 2012 cannot technically mandate the installation of smoke gasketing either for existing or new construction involving corridor doors.
The same would not hold true for fire prevention inspections conducted under the International Fire Code® for facilities constructed to meet either the IBC or the legacy Uniform Building Code (UBC) – previously adopted throughout Western Pacific regions of the US. What strategy should facility managers take about existing fire doors where edge sealing is not equipped on fire doors in their facility? Like so many things in code compliance, the answer depends on the specifics of your individual facility. If you need any assistance in understanding this parameter for your facility, AEGIS has fire protection specialists here to help you with code consulting services and inspection services that can help maintain compliance with fire door strategies.



Fire Door Safety Week 2018 - #FireDoorSafetyWeek


Fire doors are often the first line of defense in a fire and their correct installation, testing, and maintenance can be the difference between life and death for building occupants. However, these remain a significant area of neglect, often mismanaged throughout their service life, blocked open, or damaged and badly maintained. Consequently, Fire Door Safety Week was created.

For Fire Door Safety Week, TheCodeCoach.com has partnered with Aegis Fire Barrier Consultants:

  • To raise awareness of the critical role of fire doors, drawing attention to specific issues such as poor installation and maintenance.
  • To encourage building owners and users to check the operation and condition of their fire doors and to report those that aren’t satisfactory.
  • To link together the initiatives of many organizations with common interests in the fire door and passive fire protection industries.
  • To engage and educate people, helping the whole building industry and every property owner to understand the correct specification, supply, installation, operation, inspection and maintenance of fire doors.

As a resource, the presentation below presents an overview of compartmentation and the importance of fire doors. This presentation will walk you through the code requirements and applicable standards, fire door types, components and operation, and proper inspection procedures. 



National Museum of Brazil Fire [Why We Do This Job]


On the evening of September 3, 2018, the National Museum of Brazil was gutted by fire. This 200 year old institution, a former palace for the Portuguese royal family, housed more than 20-million items and artifacts. Ninety percent of these items have been lost. These items represent a past that no longer exists for Brazil, languages that are no longer spoken, skeletal remains of the earliest living humans, and 200 years of research and collected knowledge.

This tragic loss serves as a poignant reminder for the reason why we, fire prevention, protection, and life safety professionals, do this job everyday. And the importance of our role in preventing these tragedies within our communities.

Several years ago the United States Fire Administration published a document that outlined the five impacts of fire. The premise of the document was that no fire is ever “just a fire”. Fire loss, of any size, has the potential to affect the community and the organization in five distinct ways: economically, organizationally, legally, psychologically, and politically.  As the news stories and editorial pieces continue to come out on the National Museum fire, we can clearly see how these five impacts of fire are affecting the local community, the people of Brazil, and International interests.

This is evident in the headlines and stories that include the following quotes:

“...our tangible record of life on earth…”
“...destruction of careers…”
“...negligence…”
“...a crime…”
“...mismanagement…”
“...systemic neglect of cultural institutions…”

Records and reports dating back to the 1950’s show a pattern of fire protection and life safety neglect. Recent citizen complaints identified the specific hazards of flammable plastic roofing material and exposed and jury-rigged electrical wiring. Additionally, other reports state “beyond a few fire extinguishers and smoke detectors, the museum did not have a fire suppression system.”

Preliminary reports have identified the cause of the fire as originating from a paper balloon lantern or an electrical short circuit in one of the museum’s lab areas.  However, there are three core reasons, at the highest government levels, that allowed this preventable loss to happen:
  • Tight budgets and availability of funds
  • Mismanagement of money and resources
  • Neglect and lack of prioritization 
These three dangerous actions and mindsets are not unique to Brazil, but are common throughout many communities. Beyond our responsibilities related to code compliance, plan review, and fire inspections, as fire protection professionals we also have a great responsibility to mold and change mindsets of our community leaders and citizens. We must constantly work to keep investments in  fire protection and life safety at the forefront, and consistently reiterate the life altering effect and impacts that lack of these essential services and systems will lead to.